Note: All in-eld wire splices should be made using
a dry type waterproof, gel-lled Hit Products DBC-Y
type connector or equivalent.
4)
5)
Wire sizing should be of signicant size to allow a
maximum of 5 volts drop between controller and
valves. Use Ohms’ Law to calculate wire voltage
drop.
Replace cover.
Leave electrical power unattached until all valve
wires are connected to the controller.
Remove lower panel cover to gain access to the
terminal connectors. Insert the two wires from
the plug-in transformer into the two terminals
m a r k e d ‘A C “A C ”.
Replace cover.
1)
2)
3)
4
CONNECTING POWER SOURCE